Skip to content

PlanetSafe · Customer Portal

All assets

PS-GCKYA

Pallet wrapper power unit

Collins St office · Kitchen L2

Failed — action required

Test history

2 recorded events
  1. 14 May 2026FAIL

    M. Calloway · Imported from tester export

    Measurements (3)
    MeasurementValueLimit appliedOutcome
    Visual inspectionFail—FAIL
    Earth continuity0.12 Ω≤ 1.0 ΩPASS
    Insulation resistance0.62 MΩ≥ 1.0 MΩFAIL
  2. 14 Nov 2025PASS

    M. Calloway · Imported from tester export

    Measurements (3)
    MeasurementValueLimit appliedOutcome
    Visual inspectionPass—PASS
    Earth continuity0.12 Ω≤ 1.0 ΩPASS
    Insulation resistance0.62 MΩ≥ 1.0 MΩPASS

Test events are permanent records. Corrections appear as new entries that supersede the original — the original stays visible.

Failures and actions

  • Action required

    Recorded 14 May 2026

    Insulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)

Identity

PlanetSafe asset ID
PS-GCKYA
Your reference
VIC-3407
Equipment class
Class I
Site
Collins St office
Area
Kitchen L2
Retest interval
6 months
Next due
14 Nov 2026