Skip to content

PlanetSafe · Customer Portal

All reports

This version has been superseded — a newer version of this report exists in your Reports list.

Meridian Property Group · v1 · generated 14 May 2026

Visit summary

Collins St office · visit 14 May 2026

Download PDF

Share by email

Visit summary — Collins St office

A newer version of this report exists. You are sharing the superseded version — the current version is usually the right one to send.

Demo mode — you can preview the sharing workflow here. No email will be sent.

Delivery

Items tested

176

Test result: pass

168

Test result: fail

8

Test result: inconclusive

0

Failed items recorded

8

Technician

R. Okafor

Manually recorded entries

13

Visit summary
AssetItemFailure reasonStatus
PS-GCKYAPallet wrapper power unitInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)action required
PS-VWPJ5KettleInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)action required
PS-9AGYHHeat gunInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)customer notified
PS-TT68CPower board 4-wayInsulation resistance below limitaction recorded
PS-J6ZFMHot water urnInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)awaiting retest
PS-SGTV9RefrigeratorInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)awaiting retest
PS-XYFH6Sandwich pressInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)retested fail
PS-AZK4RMonitor power supplyInsulation resistance below limit (0.62 MΩ, limit ≥ 1.0 MΩ)closed

Test results are the recorded outcome of each individual portable appliance test.

Results reflect portable appliance testing carried out to AS/NZS 3760 at the date shown. Testing is one element of an electrical safety programme and does not by itself establish compliance with an organisation’s broader obligations.